Product Overview
The PDTracII 4208 instrument is the leading on-line continuous partial discharge monitor used on motors, small generators, isolated phase bus and switchgear globally.
Iris Power uses the PDTracII 4208 to collect voltage pulse data through a single 80pF Gulfsiz Epoxy Mica Capacitor per phase and analyzes the data using PDView diagnostic software to provide information need to avoid catastrophic failures, extending the life your asset and reducing the risk of unplanned outages.
All data analysis results automatically output from PDView provide information need to understand the severity and location of:
- Insulation abrasion
- Loose stator wedges
- Thermal degradation of stator insulation
- Manufacturing defects of stator bars
The results are the most repeatable and reliable information available which can also be referenced against the Iris Power severity tables which consist of a statistical review of over 700,000 machine tests globally to provide a relative health index against similar machines.
Product Overview
Motor
SwitchGear
Isolated Phase Bus
Assists with the Following Type of Monitoring
Partial Discharge Monitoring
Product Details
Features
Acquisition
- Ideally used with permanently installed Iris Power 80pF Epoxy Mica Capacitors (EMC)
- Remote inputs with 8 analog points proportional to operating conditions such as equipment temperature, voltage, current or power. These conditions are recorded for trending and analysis.
Data Analysis
- The PDTracII 4208 uses superior automatic noise separation technology based on filtering and pulse shape analysis to reliably distinguishing partial discharges from electrical interference (noise) to prevent false alarms.
- In response to a PD alert, users can review the pulse height analysis plots, and the 24-window phase resolved PD plots using basic interpretation to confirm the cause of the alert
Communication
- The PDTracII 4208 can operate “stand alone” system with only periodic downloading of archived partial discharge data or it can be networked into the plant control system for remote data acquisition and analysis through USB, Ethernet or Modbus.
- An alert output using a dedicated relay can activate a remote indicator of high partial discharge alert conditions. The alert output may also be connected to a plant monitoring system.
Options
Data Acquisition
- Local ambient humidity and temperature sensor.
- Configuration suitable to work with existing low frequency capacitive couplers (1nF – 2 nF)
Certifications
ATEX/IECEx
II 3G Ex nA nC IIC T4 Gc in compliance with
EN 60079-0:2012/A11:2013,
EN 60079-15:2010
IEC 60079-0:2011 Ed. 6
IEC 60079-15:2011 Ed. 4
C-US
Class I, Division 2, Groups A, B, C, D T4
Ex nA nC IIC T4 Gc
Class I, Zone 2, AEx nA nC IIC T4 Gc based on
CAN/CSA C22.2 No. 61010-1-12
CSA Std. C22.2 No. 213-16
CAN/CSA-C22.2 No. 60079-0:15
CAN/CSA-C22.2 No. 60079-15:16
ANSI/UL 61010-1, 3rd Ed
ANSI/ISA-12.12.01-2015
ANSI/UL 60079-0:13
ANSI/UL 60079-15:13
INMETRO
Ex nA nC IIC T4 Gc
In compliance with
ABNT NBR ISO IEC 60079-0:2013
ABNT NBR ISO IEC 60079-15:2012
- Other country certifications may be available.
Communication